How To Repair A Hole In The Heat Exchanger

  1. Temporary repair of heat exchanger - JB Weld ?

    We have a gas pack that has a estrus exchanger with a spot that is rusting - about the size of dime - and at the eye is a small-scale pin tip area that looks about fix to requite way. Nosotros want to exercise a temporary prepare for a few months until atmospheric condition warms upwards and contractors are less decorated. No elevated carbon dioxide levels in abode - but a gassy smell at the unit exhaust. Was told this means the exchanger is on it's last legs and other causes were ruled out.

    Would JB Weld agree up to the oestrus of the exchanger - or some other product? Trane ii ton gas pack dated 1999. Used to encounter commercials for something chosen "Allumaloy" - but call back that requires welding.


  2. BAD idea, if y'all do this it volition put the lives of anyone in the habitation at hazard!

  3. Quote Originally Posted by siriuse View Post

    BAD idea, if y'all do this it will put the lives of anyone in the home at adventure!

    Tin you delight explicate why ?

  4. Quote Originally Posted by cbc58 View Post

    Can you please explain why ?

    If you knew y'all wouldn't ask that type of question.

  5. Typical this time of year when the gaspac'due south run a long bike and the Truth comes along.
    There is no 'fixing' of a bad HX exterior of replacement of it or the unit.
    Period,Stop,Cease of discussion.
    We let it run,You die,Hospital,Lawyer's,
    Story never cease'due south well for Everyone.
    Y'all,Should have Whatsoever 'Gas Heating Unit' checked annually BEFORE it become's Cold and You are 'Without,'When.

  6. Time to lock this one upwards.

    UA Local 32 retired as of Jan 2022


  7. Why?
    These are Factory designed,formed,welded 'pieces' which Nosotros are NOT 'allowed' to gear up.
    L-I-A-B-I-L-I-T-Y.......
    Nosotros 'try' to repair them,
    Nosotros Assume the liability of Your LIFE. And we are not GOD.
    10-4.

  8. Replace the HX, or unit now. Waiting just increases the chances of health problems.

  9. A crack or small hole is a FAILED HEAT EXCHANGER. None of us can tell you it's ok to patch it. We can tell you it'south a failed function and needs to be replaced. Either the heat exchanger or the furnace. No getting around it. If your fan motor failed and you asked if y'all could put a paw crank on information technology and manually spin it for a few months I'm certain people would say, "Sure go ahead, the furnace has limit controls to protect against over temping" just the furnace has no protection for carbon monoxide leakage (non carbon dioxide). The merely protection is a sound heat exchanger, that's it'due south task, if it'due south bankrupt information technology tin't do it's chore.

    ckartson
    I didn't write the book I only read it!


  10. I appreciate folks in the trade not wanting to set a heat exchanger for liability purposes. But that'south not what I asked and wanted to know if some grade of temporary patch can be practical.

    If there is no CO2 upshot at present - what is the problem ?

    I am just request because I am a homeowner and the "just buy a new one" doesn't fit into our budget right at present. Accept to believe this is a common problem out there.


  11. You take been given more than information than virtually DIY questions become, the issue is you are not taking it. Go your budget in order and get a new heat exchanger or complete unit. I retrieve that is all you will become here.

    UA Local 32 retired as of Jan 2022


  12. You lot can have just the heat exchanger replaced.

  13. Quote Originally Posted by cbc58 View Post

    I appreciate folks in the trade not wanting to set a rut exchanger for liability purposes. But that's non what I asked and wanted to know if some class of temporary patch tin can exist applied.

    If there is no CO2 issue now - what is the problem ?

    I am just asking because I am a homeowner and the "just buy a new one" doesn't fit into our budget correct now. Have to believe this is a common problem out in that location.

    The "folks in the trade" are experts. The answer from the experts is an emphatic No. At that place is no temporary fix. You run a risk the prophylactic of all in the house if yous try some cockamamie repair. To repeat an earlier correction, CO2 is non a concern. CO is a very real business.
    I promise that is clear plenty for yous.

    *********
    https://www.hvac20.com/ Loftier efficiency equipment alone does not provide dwelling comfort and efficiency. HVAC2.0 is a process for finding the real needs of the house and the occupants. Offer the customer a menu of work to address their problems and give them a probability of success.

    Find contractors with specialized training in combustion assay, residential organisation operation, air catamenia, and duct optimization

    https://www.myhomecomfort.org/


    Site member map Here!


  14. You land you accept no elevated CO2 in the habitation...

    The result has NOTHING TO DO WITH CO2...

    The event is with the Blood POISIONING Chemic CO WHICH IS CARBON MONOXIDE... the hole does two things, it alters the oxygen mix feeding the flame resulting in a high CO production, and the hole allows the concentrated mix of the chemical into the home.

    NO. NO. NO. YOU CANNOT SAFELY REPAIR THE HOLE...

    Yous MUST REPLACE THE HEAT EXCHANGER OR THE FURNACE, OR ENDANGER YOURSELF, AND YOUR Family.

    Period!


  15. Quote Originally Posted by cbc58 View Post

    I appreciate folks in the trade not wanting to set a estrus exchanger for liability purposes. Just that's non what I asked and wanted to know if some grade of temporary patch tin be applied.

    If there is no CO2 issue now - what is the problem ?

    I am just asking because I am a homeowner and the "only buy a new i" doesn't fit into our budget right now. Accept to believe this is a common problem out there.

    How do you know there'south no CO leakage considering the detectors oasis't gone off? Dwelling house detectors trip at to high a setting. 50PPM or higher all the same low levels are dangerous.

    Get the unit repaired or replaced. Your life depends on information technology


  16. Folks that have estrus exchanger failure and tin can't afford to repair or supersede it at the fourth dimension accept few options. Offset option is finish the season with space heaters. 2d option is utilize for state or local assistance. Financing is a 3rd choice only that one might require working a second task .

  17. Cracked or compromised estrus exchanger presents a burn and CO run a risk. Hacking "temporary" repairs elevates those risks and could even drag them.
    Afterward you slap a pile of goo on the old exchanger what do yous remember will happen to the hot spot you only created?
    There is no "cheap" way effectually information technology. Doing something similar you ask is incredibly stupid and puts your family'southward lives in danger and puts your dwelling house at risk of fire.
    Why not telephone call the makers of JB and inquire them if their product is rated for gas fired heat exchangers? Encounter what they have to say.

    �I haven�t failed. I�ve but found 10,000 means that won�t work.� - Thomas Edison

    �Information technology�due south not whether you lot get knocked downwards, it�southward whether you become upward.� - Vince Lombardi

    "In this business firm we obey the laws of thermodynamics" - Homer Simpson

    Local 486 Instructor & Service Technician


  18. Quote Originally Posted by beenthere View Post

    Replace the HX, or unit at present. Waiting simply increases the chances of health issues.

    As a moderator, you lot should have made this annotate, then locked the thread for DIY and potential death.

  19. Basically isn't JB weld just plastic? Doesn't plastic melt and or cause toxic fumes?
    In that location is NO rubber fashion to practise what you want. There is no one on this forum who would recommend any kind of unsafe fix. This is the best answer we could give you.

    Quote Originally Posted by cbc58 View Post

    I appreciate folks in the merchandise non wanting to ready a estrus exchanger for liability purposes. But that'due south not what I asked and wanted to know if some form of temporary patch can be practical.

    If in that location is no CO2 issue now - what is the problem ?

    I am just request because I am a homeowner and the "just buy a new one" doesn't fit into our budget correct now. Have to believe this is a mutual trouble out there.


  20. http://www.amazon.com/Honeywell-Ener...RTABLE+HEATERS

    2-3 of these will become y'all by ,also face up it if a temp repair was avalible you would not fix it right


Source: https://hvac-talk.com/vbb/threads/1878411-Temporary-repair-of-heat-exchanger-JB-Weld